BVN Air USA

When airflow is lower than expected, the useful question is where the system is losing pressure. A calculation helps estimate those losses before installation. Field measurements help locate restrictions once the system is running.

Static pressure is the air pressure measured without the contribution of air velocity. In practice, static-pressure readings help assess the resistance associated with ducts, filters and other components.

1. Build a pressure-loss budget

Start with the required airflow and the proposed duct layout. Pressure losses must be evaluated at that airflow: a value calculated for one flow rate cannot simply be reused for another.

For each airflow path, record:

  • Straight duct lengths, sizes and material.
  • Elbows, transitions and branch fittings.
  • Filters and their specified final pressure drop.
  • Dampers, grilles, silencers and exterior terminations.

Calculate straight-duct loss using a duct calculator or friction chart:

Straight-duct loss = friction rate × duct length

If the friction rate is expressed per 100 feet, divide the duct length by 100 before multiplying.

Use fitting data that match the actual geometry and airflow. An elbow’s loss depends on its design; there is no single pressure drop that applies to every elbow.

For filters, dampers and other accessories, use the manufacturer’s pressure-drop data. Avoid counting a component twice if its loss is already included in the equipment rating.

For a branched system, evaluate the most demanding complete airflow path. Do not add the losses from every parallel branch together.

2. A worked calculation

Consider a simple, single-path exhaust system designed for 500 CFM. Assume the following illustrative losses at that airflow:

ComponentAssumed pressure loss
40 ft of straight duct at 0.20 in. wg per 100 ft0.08 in. wg
Two elbows at 0.06 in. wg each0.12 in. wg
Filter at its specified final pressure drop0.20 in. wg
Backdraft damper0.08 in. wg
Exterior hood0.10 in. wg
Total component losses0.58 in. wg

The straight-duct calculation is:

0.20 × (40 ÷ 100) = 0.08 in. wg

The listed losses add up to 0.58 in. wg, or approximately 144 Pa.

These are assumed values for demonstrating the method, not standard values for these components. Actual losses must come from the selected duct geometry and accessory data.

The result is a pressure-loss budget. Before using it for fan selection, confirm the manufacturer’s pressure basis and installation arrangement. Outlet velocity pressure, any required room-pressure difference and installation effects may also need to be accounted for.

3. Measure static pressure in the field

Use a differential manometer with proper static-pressure probes.

  1. Choose the test locations. Follow the equipment manufacturer’s instructions. Use representative duct sections and avoid disturbed airflow near elbows or abrupt transitions where possible.
  2. Zero the instrument. Follow the manometer’s procedure with the tubing and probes connected as instructed.
  3. Position the probes correctly. Follow the probe manufacturer’s orientation guidance; an open tube facing into the airflow can pick up velocity pressure.
  4. Run the system under documented conditions. Record fan speed, damper positions and filter condition.
  5. Record signed readings. Inlet or return pressure may be negative relative to the reference pressure; outlet or supply pressure may be positive.

For example, readings of −0.18 in. wg and +0.32 in. wg give a static-pressure difference of:

0.32 − (−0.18) = 0.50 in. wg

At the manufacturer’s designated external test points, this can represent total external static pressure for the equipment. Across a standalone fan, the static-pressure difference is not automatically the fan static pressure used in its catalogue; velocity-pressure corrections and measurement locations matter.

4. Use component measurements to find restrictions

Measure immediately upstream and downstream of a filter, in sections with comparable air velocity.

If the readings are −0.10 in. wg upstream and −0.30 in. wg downstream, the filter pressure drop is:

−0.10 − (−0.30) = 0.20 in. wg

Compare the result with the filter manufacturer’s data at the actual airflow and its recommended replacement limit. A high reading alone does not prove the filter is dirty; airflow and filter type also affect pressure drop.

Static pressure does not directly measure airflow. Verify airflow separately using an appropriate method, such as a duct traverse or a calibrated airflow station.

Calculate the losses before installation. Measure individual components during commissioning. Together, these steps show where pressure is being used and where corrective work will help.

Follow Us on LinkedIn